Primary Connectors

FAA L-823, Styles 3 and 10, Class B

Primary Connectors are available for screened (shielded) and unscreened (unshielded) cable.
All of our Primary Connectors comply with the appropriate FAA 5345-26 requirements for plugs and receptacles (cable connectors).
Efla’s Primary Connectors are packed and delivered in kits including all the necessary parts for making the assembly on primary cables. Each Primary Connector kit contains parts for a pair (a plug and a receptacle), resulting in a watertight post-installation connection.
Nominal rating: 25 A and 5 000V



FOR SCREENED CABLES



KD 500 -series   KDR 600, Resin type
 
Quick installation with conductive parts, screen continuity and insulation parts filled with silicon grease.   Resin-type Primary Connector for heavy-duty use. Efla’s resin type connector is supplied with a high performance PU resin to be poured inside the insulation body around the connective parts and screen continuity.

KD 500 KD 500/YG KD 500/B

Screen continuity

The standard screen continuity is a 2.5 mm² tinned
copper wire, 300 mm long. Upon request, KD 500 and KDR 600 may be supplied with insulated screen continuity in yellow-green (e.g. KD 500/YG) or black (e.g. KDR 600/B). 6 mm² is also available.

MORE TECHNICAL DATA OF PRIMARY CONNECTORS



Dimensional data

Conductor Size mm² AWG Cable Diameter in inches Diameter at wire insulation in inches Diameter, Length of assembly in inches Efla Type
6 mm² 8 *)*) 10.0 – 14.5 mm 0,393 – 0,570 7.0 – 10.5 mm 0,275 – 0,413 23,5mm, 222 mm 0,925in, 8,74in KD 500
6 mm² 8 *)*) 14.0 – 18.5 mm 0,551 – 0,728 10.0 – 13.5 mm 0,393 – 0,531 23,5mm, 222 mm 0,925in, 8,74in KD 500.1
6 mm² 8 *)*) 18.0 – 22.0 mm 0,708 – 0,866 12.5 – 16.0 mm 0,492 – 0,629 23,5mm, 215 mm 0,925in, 8,46in KD 500.3
6 mm² 8 *)*) 8.5 – 11.5 mm 0,334 – 0,452 5.0 – 7.5 mm 0,196 – 0,295 23,5mm, 222 mm 0,925in, 8,74in KD 500.6
10 mm² *) 6 14.0 – 18.5 mm 0,551 – 0,728 10.0 – 13.5 mm 0,393 – 0,531 23,5mm, 222 mm 0,925in, 8,74in KD 500.2
10 mm² *) 6 18.0 – 22.0 mm 0,708 – 0,866 12.5 – 16.0 mm 0,492 – 0,629 23,5mm, 215 mm 0,925in, 8,46in KD 500.4
10 mm² *) 6 10.0 – 14.5 mm 0,393 – 0,570 7.0 – 10.5 mm 0,275 – 0,413 23,5mm, 222 mm 0,925in, 8,74in KD 500.5
6 mm² 8 *)*) 9.0 – 19.0 mm 0,354 – 0,748 7.0 – 10.5 mm 0,275 – 0,413 31,0mm, 270 mm 1,22in, 10,62in KDR 600
10 mm² *) 6 9.0 – 19.0 mm 0,354 – 0,748 5.0 – 7.5 mm 0,196 – 0,295 31,0mm, 270 mm 1,22in, 10,62in KDR 600.2

*) 16 mm² stranded *)*) up to 19 strands



FOR UNSCREENED CABLES



KD 510 -series   KDR 610, Resin type

 
Quick installation with conductive and insulation parts filled with silicon grease.   Resin-type Primary Connector for heavy-duty use. Efla’s resin type connector is supplied with a high performance PU resin to be poured inside the insulation body around the connective parts.


Conductor Size mm² AWG Cable Diameter in inches Diameter at wire insulation in inches Diameter, Length of assembly in inches Efla Type
6 mm² 8 *)*) 10.0 – 14.5 mm 0,393 – 0,570 7.0 – 10.5 mm 0,275 – 0,413 23,5 mm, 222 mm 0,925in, 8,74in KD 510
6 mm² 8 *)*) 14.0 – 18.5 mm 0,551 – 0,728 10.0 – 13.5 mm 0,393 – 0,531 23,5 mm, 222 mm 0,925in, 8,74in KD 510.1
6 mm² 8 *)*) 18.0 – 22.0 mm 0,708 – 0,866 12.5 – 16.0 mm 0,492 – 0,629 23,5 mm, 215 mm 0,925in, 8,46in KD 510.3
6 mm² 8 *)*) 8.5 – 11.5 mm 0,334 – 0,452 5.0 – 7.5 mm 0,196 – 0,295 23,5 mm, 222 mm 0,925in, 8,74in KD 510.6
10 mm² *) 6 14.0 – 18.5 mm 0,551 – 0,728 10.0 – 13.5 mm 0,393 – 0,531 23,5 mm, 222 mm 0,925in, 8,74in KD 510.2
10 mm² *) 6 18.0 – 22.0 mm 0,708 – 0,866 12.5 – 16.0 mm 0,492 – 0,629 23,5 mm, 215 mm 0,925in, 8,46in KD 510.4
10 mm² *) 6 10.0 – 14.5 mm 0,393 – 0,570 7.0 – 10.5 mm 0,275 – 0,413 23,5 mm, 222 mm 0,925in, 8,74in KD 510.5
6 mm² 8 *)*) 9.0 – 19.0 mm 0,354 – 0,748 7.0 – 10.5 mm 0,275 – 0,413 31,0 mm, 270 mm 1,22in, 10,62in KDR 610
10 mm² *) 6 9.0 – 19.0 mm 0,354 – 0,748 5.0 – 7.5 mm 0,196 – 0,295 31,0 mm, 270 mm 1,22in, 10,62n KDR 610.2

*) 16 mm² stranded *)*) up to 19 strands