Agl Series Transformers

Efla’s AGL transformers are designed and manufactured to meet the requirements of IEC 61823, FAA AC 150/5345-47B and ICAO Aerodrome Design Manual: Part 5 Electrical Systems. The transformers are available from 30/45 W to 300 W, alternatively with or without earthing. Toroidal core has the optimal shape for a transformer which allows a design with excellent properties. All transformers are exposed to comprehensive test procedure.

AGL series transformers are equipped with primary connectors FAA –L 823 Style 2 and Style 9. Standard length of primary leads is 0,6m. The length of the secondary lead is 1,2m containing either FAA-L823 Style7 (standard) or Style 8 connector.

kr551_cu

Test Results

All test results are recorded and can be supplied with the delivery if EFLA is informed when ordered.

Afterwards Test reports can be supplied only if the id-number of transformer is informed to EFLA (Sticker on secondary lead).
Efla Type FAA Type Nominal
Rating
[W]
Current
Rating
[A]
Max Primary
Circuit
Voltage
[V]
Frequency
[Hz]
Min PF
With
Earthing
Without
Earthing

ETL CERTIFIED




KR 531 KR 531.1 L-830-1
L-831-1
30/45 6.6/6.6 5000 50/60 0.97
KR 536 KR 536.1 L-830-3
L-831-3
65 6.6/6.6 5000 50/60 0.97
KR 541 KR 541.1 L-830-4
L-831-4
100 6.6/6.6 5000 50/60 0.97
KR 546 KR 546.1 L-830-19
L-831-19
150 6.6/6.6 5000 50/60 0.97
KR 551 KR 551.1 L-830-6
L-831-6
200 6.6/6.6 5000 50/60 0.97
KR 561 KR 561.1 L-830-10
L-831-10
300 6.6/6.6 5000 50/60 0.97
Available also with current ratings 20A/6,6A and 8.3A/6,6A. (Efla types for example KR531.20 and KR551.83.1)
More information